Unit of Measure
Items
IPAQ-L / IPAQ-LX Universal Programmable 2-Wire Transmitters

IPAQ-L Universal Programmable 2-Wire Transmitter

IPAQ-L / IPAQ-LX Universal Programmable 2-Wire Transmitters

IPAQ-LX Universal Programmable 2-Wire Transmitter

IPAQ-L Plus / IPAQ-LX Plus High-Precision Universal Programmable 2-Wire Transmitter

IPAQ-L Plus High-Precision Universal Programmable 2-Wire Transmitter

IPAQ-L Plus / IPAQ-LX Plus High-Precision Universal Programmable 2-Wire Transmitter

IPAQ-LX Plus High-Precision Universal Programmable 2-Wire Transmitter
Description N/A IPAQ-L / -LX are universal, isolated 2-wire transmitters for temperature and other measurement applications. They combine competitive pricing, functionality and simple configuration. N/A IPAQ-L / -LX are universal, isolated 2-wire transmitters for temperature and other measurement applications. They combine competitive pricing, functionality and simple configuration. N/A IPAQ-L Plus / -LX Plus offer the highest performance available today regarding accuracy, speed and functionality. N/A IPAQ-L Plus / -LX Plus offer the highest performance available today regarding accuracy, speed and functionality.
Input RTD - D 100 (α = 0.00385), 3-, 4-Wire Connection1 N/A -200 to +1000 ºC-328 to +1832 ºF
Input RTD - Ni 100 (DIN 43760), 3-, 4-Wire Connection N/A -60 to +250 ºC-76 to +482 ºF
Input RTD - Ni 1000 (DIN 43760), 3-, 4-Wire Connection N/A -60 to +150 ºC-76 to +302 ºF
Input RTD - Pt 100 (α = 0.00385), 3-, 4-Wire Connection2 N/A -200 to +1000 ºC-328 to +1832 ºF
Input RTD - Pt 1000 (α = 0.00385), 3-, 4-Wire Connection N/A -200 to +200 ºC-328 to +392 ºF
Input RTD - PtX 10 ≤ X ≤ 1000 (α = 0.00385), 3-, 4-Wire Connection3 N/A Upper Range Depending on X-value
Potentiometer / Resistance N/A 0 to 2000 Ohm
Input Thermocouple Type N/A AE, B, E, J, K, L, N, R, S, T, U
Input Voltage N/A -10 to +500 mV
Input Current4 N/A - 1 to +50 mA N/A - 1 to +50 mA N/A N/A
Sensor Failure / Low Isolation N/A User Definable Output / N/A N/A User Definable Output / N/A N/A User Definable Output / User Definable Output N/A User Definable Output / User Definable Output
Zero Adjustment N/A Any Value within Range Limits
Min. Span N/A Pt100, Pt1000, Ni100, Ni1000 18 ºFPt100, Pt1000, Ni100, Ni1000 10 ºCT/C 2 mVPotentiometer 10 Ohm
Output N/A 4 to 20 mA / 20 to 4 mA
Operating Temperature N/A -4 to 158 ºF-20 to 70 ºC
Galvanic Isolation N/A 1500 VAC, 1 min N/A 1500 VAC, 1 min N/A 3750 VAC, 1 min N/A 3750 VAC, 1 min
Power Supply N/A 7.5 to 36 VDC N/A 8 to 30 VDC N/A 7.5 to 36 VDC N/A 8 to 30 VDC
Intrinsic Safety (Mounting in Safe Area)5 N/A N/A ATEX II (1) Cenelec: [EEx ia] IIC FM, CSA Class I - III, Div. 1, Groups A to G N/A N/A ATEX II (1) Cenelec: [EEx ia] IIC FM, CSA Class I - III, Div. 1, Groups A to G
Typical Accuracy N/A ±0.1 % of Temperature Span N/A ±0.1 % of Temperature Span N/A ±0.05 % of Temperature Span N/A ±0.05 % of Temperature Span
Mounting N/A Rail Acc. to DIN EN 50022, 35 mm
Features N/A
  • Fully universal, linearized and isolated
  • Accepts RTD, TIC, mV and Ohm
  • Sensor and system error correction
  • Full access to all features while in operation
  • NAMUR Compliant
  • Consistent sensor break function
  • Simplified loop check-up with calibration output
  • Test output without breaking the loop
  • IPRO, Easy to use Windows configuration software IPAQ-L Plus / LX Plus
  • Extra high accuracy, stability and isolation
  • 40 point linearization - any sensor can be matched
  • Configuration without external power
  • High speed, Smart filter, Display connection
  • Selectable Floor and Ceiling
  • Low sensor isolation detection
  • 1 Pt100 Acc. to IIS1604, α = 0.003916
  • 2 Pt100 Acc. to IIS1604, α = 0.003916
  • 3 IEC751, α = 0.00385
  • 4 Separate Version of iPAQ-L, Only for Current Input
  • 5 Connections to Ex Area